.\" Process this file with
|
|
.\" groff -man -Tascii bacwp.1
|
|
.\" Contact <skarg@users.sourceforge.net> to correct errors or ommissions
|
|
.TH bacwp 1 "Sept 16 2011" "0.7.0" "BACnet Stack at SourceForge Tool Manual"
|
|
.SH NAME
|
|
bacwp \- send BACnet WriteProperty service request to a BACnet device
|
|
.SH SYNOPSIS
|
|
|
|
.B bacwp device-instance object-type object-instance property priority index tag value [tag value...]
|
|
|
|
.SH DESCRIPTION
|
|
.B bacrp uses the BACnet WriteProperty service request to write
|
|
a property value to a BACnet device on the network. WhoIs and
|
|
I-Am are used for device binding. A simple Ack or error message
|
|
is returned to stdio.
|
|
|
|
.SH OPTIONS
|
|
.IP device-instance
|
|
Device object instance number that you are trying to
|
|
send a WriteProperty service request. The value should be in
|
|
the range of 0 to 4194303.
|
|
|
|
.IP "object-type"
|
|
The object type is the integer value of the enumeration
|
|
BACNET_OBJECT_TYPE in bacenum.h. It is the object
|
|
that you are writing. For example if you were
|
|
writing Analog Output 2, the object-type would be 1.
|
|
|
|
.IP "object-instance"
|
|
This is the object instance number of the object that
|
|
you are writing. For example, if you were writing
|
|
Analog Output 2, the object-instance would be 2.
|
|
|
|
.IP "property"
|
|
The property is an integer value of the enumeration
|
|
BACNET_PROPERTY_ID in bacenum.h. It is the property
|
|
you are writing. For example, if you were writing the
|
|
Present Value property, the property is 85.
|
|
|
|
.IP "priority"
|
|
|
|
This parameter is used for setting the priority of the
|
|
write. If Priority 0 is given, no priority is sent. The BACnet
|
|
standard states that the value is written at the lowest
|
|
priority (16) if the object property supports priorities
|
|
when no priority is sent.
|
|
|
|
.IP "index"
|
|
This integer parameter is the index number of an array.
|
|
If the property is a BACnetARRAY and writable, individual
|
|
elements can be written. If this parameter value is -1,
|
|
it is omitted when writing to the property.
|
|
|
|
.IP "tag"
|
|
Tag is the integer value of the enumeration BACNET_APPLICATION_TAG
|
|
in bacenum.h. It is the data type of the value that you are
|
|
writing. For example, if you were writing a REAL value, you would
|
|
use a tag of 4.
|
|
Context tags are created using two tags in a row. The context tag
|
|
is preceded by a C. Ctag tag. C2 4 creates a context 2 tagged REAL.
|
|
|
|
.IP "value"
|
|
The value is an ASCII representation of some type of data that you
|
|
are writing. It is encoded using the tag information provided. For
|
|
example, if you were writing a REAL value of 100.0, you would use
|
|
100.0 as the value. If you were writing an Object-Identifier such
|
|
as Device object 1, you would use 8:1 as the value. If you were
|
|
writing a Boolean, a value of 0 would indicate false, and a non-zero
|
|
value would indicate true.
|
|
|
|
|
|
.SH BACnet Tags
|
|
Here is a brief overview of BACnet property and tags:
|
|
Certain properties are expected to be written with certain
|
|
application tags, so you probably need to know which ones to use
|
|
with each property of each object. It is almost safe to say that
|
|
given a property and an object and a table, the tag could be looked
|
|
up automatically. There may be a few exceptions to this, such as
|
|
the Any property type in the schedule object and the Present Value
|
|
accepting REAL, BOOLEAN, NULL, etc. Perhaps it would be simpler for
|
|
the demo to use this kind of table - but I also wanted to be able
|
|
to do negative testing by passing the wrong tag and have the server
|
|
return a reject message.
|
|
|
|
.SH EXAMPLES
|
|
If you want send a value of 100 to the Present-Value in
|
|
Analog Output 0 of Device 123 at priority 16,
|
|
send the following command:
|
|
$ bacwp 123 1 0 85 16 -1 4 100
|
|
To send a relinquish command to the same object:
|
|
$ bacwp 123 1 0 85 16 -1 0 0
|
|
|
|
.SH FILES
|
|
.I address_cache
|
|
.RS
|
|
A cache that is read for static binding. See
|
|
.BR address_cache (5)
|
|
for further details.
|
|
.SH ENVIRONMENT
|
|
.IP BACNET_IP_PORT
|
|
If non-null, the number of the UDP port for BACnet/IP datalink.
|
|
The default UDP port number is 47808 (0xBAC0).
|
|
.IP BACNET_IFACE
|
|
If non-null, the device name for the datalink.
|
|
The default is "eth0".
|
|
.IP BACNET_BBMD_PORT
|
|
If non-null, the number of the UDP port that the BBMD is using.
|
|
The default UDP port number is 47808 (0xBAC0).
|
|
Used for BACnet/IP datalink only.
|
|
.IP BACNET_BBMD_TIMETOLIVE
|
|
If non-null, the number of seconds used in the Foreign Device
|
|
Registration. A 16-bit unsigned value of 0 to 65535 is expected.
|
|
The default number of seconds is 65535 (0xFFFF).
|
|
Used for BACnet/IP datalink only.
|
|
.IP BACNET_BBMD_ADDRESS
|
|
If non-null, the IP address of the BBMD that is handling the
|
|
Foreign Device Registration. If this environment variable is
|
|
missing or NULL, then Foreign Device Registration does not occur.
|
|
Used for BACnet/IP datalink only.
|
|
.IP BACNET_MAX_INFO_FRAMES
|
|
If non-null, the Max-Info-Frames value between 1 and 255.
|
|
The default number of frames is 1.
|
|
Used for BACnet MS/TP datalink only.
|
|
.IP BACNET_MAX_MASTER
|
|
If non-null, the Max-Master value between 1 and 127.
|
|
The default Max-Master is 127.
|
|
Used for BACnet MS/TP datalink only.
|
|
.IP BACNET_MSTP_BAUD
|
|
If non-null, a value baud rate of 9600, 19200, 38400, 57600,
|
|
and 115200.
|
|
The default baud rate is 9600.
|
|
Used for BACnet MS/TP datalink only.
|
|
.IP BACNET_MSTP_MAC
|
|
If non-null, the MS/TP MAC address value between 0 and 127.
|
|
The default MAC address is 0.
|
|
Used for BACnet MS/TP datalink only.
|
|
|
|
.SH DIAGNOSTICS
|
|
The following diagnostics may be issued on stderr:
|
|
|
|
device-instance=x - it must be less than 4194304
|
|
object-type=x - it must be less than 1024
|
|
object-instance=x - it must be less than 4194304
|
|
property=x - it must be less than 4194304
|
|
Error: not enough tag-value pairs
|
|
Error: tag=x - it must be less than 15
|
|
Error: unable to parse the tag value
|
|
Error: Exceeded 64 tag-value pairs.
|
|
Error: TSM Timeout!
|
|
Error: APDU Timeout!
|
|
|
|
.SH BUGS
|
|
No bugs are known to exist at this time.
|
|
.SH AUTHOR
|
|
Steve Karg <skarg@users.sourceforge.net>
|
|
.SH "SEE ALSO"
|
|
.BR bacarf (1),
|
|
.BR bacawf (1),
|
|
.BR bacdcc (1),
|
|
.BR bacepics (1),
|
|
.BR bacrd (1),
|
|
.BR bacrp (1),
|
|
.BR bacserv (1),
|
|
.BR bacts (1),
|
|
.BR bacucov (1),
|
|
.BR bacwh (1),
|
|