#!/usr/bin/env python
|
|
# -*- coding: utf-8 -*-
|
|
|
|
"""
|
|
Test Pulse Converter COV Services
|
|
---------------------------------
|
|
"""
|
|
|
|
import unittest
|
|
|
|
from bacpypes.debugging import bacpypes_debugging, ModuleLogger
|
|
|
|
from bacpypes.primitivedata import Date, Time
|
|
from bacpypes.basetypes import DateTime
|
|
|
|
from bacpypes.apdu import (
|
|
SubscribeCOVRequest, SimpleAckPDU,
|
|
ConfirmedCOVNotificationRequest, UnconfirmedCOVNotificationRequest,
|
|
)
|
|
|
|
from bacpypes.service.cov import ChangeOfValueServices
|
|
from bacpypes.local.device import LocalDeviceObject
|
|
from bacpypes.object import PulseConverterObject
|
|
|
|
from .helpers import ApplicationNetwork, ApplicationStateMachine, COVTestClientServices
|
|
|
|
# some debugging
|
|
_debug = 0
|
|
_log = ModuleLogger(globals())
|
|
|
|
|
|
@bacpypes_debugging
|
|
class TestPulseConverter(unittest.TestCase):
|
|
|
|
def test_8_10_1(self):
|
|
"""Confirmed Notifications Subscription"""
|
|
if _debug: TestPulseConverter._debug("test_8_10_1")
|
|
|
|
# create a network
|
|
anet = ApplicationNetwork("test_8_10_1")
|
|
|
|
# add the ability to accept COV notifications to the TD
|
|
anet.td.add_capability(COVTestClientServices)
|
|
|
|
# tell the TD how to respond to confirmed notifications
|
|
anet.td.test_ack = True
|
|
anet.td.test_reject = None
|
|
anet.td.test_abort = None
|
|
|
|
# add the service capability to the IUT
|
|
anet.iut.add_capability(ChangeOfValueServices)
|
|
|
|
# make a pulse converter object
|
|
test_pc = PulseConverterObject(
|
|
objectIdentifier=('pulseConverter', 1),
|
|
objectName='pc',
|
|
presentValue=0.0,
|
|
statusFlags=[0, 0, 0, 0],
|
|
updateTime=DateTime(date=Date().now().value, time=Time().now().value),
|
|
covIncrement=10.0,
|
|
covPeriod=10,
|
|
)
|
|
|
|
# add it to the implementation
|
|
anet.iut.add_object(test_pc)
|
|
|
|
# wait for the subscription
|
|
anet.iut.start_state.doc("8.10.1-1-0") \
|
|
.receive(SubscribeCOVRequest).doc("8.10.1-1-1") \
|
|
.success()
|
|
|
|
# send the subscription, wait for the ack
|
|
anet.td.start_state.doc("8.10.1-2-0") \
|
|
.send(SubscribeCOVRequest(
|
|
destination=anet.iut.address,
|
|
subscriberProcessIdentifier=1,
|
|
monitoredObjectIdentifier=('pulseConverter', 1),
|
|
issueConfirmedNotifications=True,
|
|
lifetime=30,
|
|
)).doc("8.10.1-2-1") \
|
|
.receive(SimpleAckPDU).doc("8.10.1-2-2") \
|
|
.success()
|
|
|
|
# run the group
|
|
anet.run()
|
|
|
|
def test_8_10_2(self):
|
|
"""Unconfirmed Notifications Subscription"""
|
|
if _debug: TestPulseConverter._debug("test_8_10_2")
|
|
|
|
# create a network
|
|
anet = ApplicationNetwork("test_8_10_2")
|
|
|
|
# add the ability to accept COV notifications to the TD
|
|
anet.td.add_capability(COVTestClientServices)
|
|
|
|
# tell the TD how to respond to confirmed notifications
|
|
anet.td.test_ack = True
|
|
anet.td.test_reject = None
|
|
anet.td.test_abort = None
|
|
|
|
# add the service capability to the IUT
|
|
anet.iut.add_capability(ChangeOfValueServices)
|
|
|
|
# make a pulse converter object
|
|
test_pc = PulseConverterObject(
|
|
objectIdentifier=('pulseConverter', 1),
|
|
objectName='pc',
|
|
presentValue=0.0,
|
|
statusFlags=[0, 0, 0, 0],
|
|
updateTime=DateTime(date=Date().now().value, time=Time().now().value),
|
|
covIncrement=10.0,
|
|
covPeriod=10,
|
|
)
|
|
|
|
# add it to the implementation
|
|
anet.iut.add_object(test_pc)
|
|
|
|
# wait for the subscription
|
|
anet.iut.start_state.doc("8.10.2-1-0") \
|
|
.receive(SubscribeCOVRequest).doc("8.10.2-1-1") \
|
|
.success()
|
|
|
|
# send the subscription, wait for the ack
|
|
anet.td.start_state.doc("8.10.2-2-0") \
|
|
.send(SubscribeCOVRequest(
|
|
destination=anet.iut.address,
|
|
subscriberProcessIdentifier=1,
|
|
monitoredObjectIdentifier=('pulseConverter', 1),
|
|
issueConfirmedNotifications=False,
|
|
lifetime=30,
|
|
)).doc("8.10.2-2-1") \
|
|
.receive(SimpleAckPDU).doc("8.10.2-2-2") \
|
|
.success()
|
|
|
|
# run the group, cut the time limit short
|
|
anet.run(time_limit=5.0)
|
|
|
|
# check that the IUT still has the detection
|
|
if _debug: TestPulseConverter._debug(" - detections: %r", anet.iut.cov_detections)
|
|
assert len(anet.iut.cov_detections) == 1
|
|
|
|
# pop out the subscription list and criteria
|
|
obj_ref, criteria = anet.iut.cov_detections.popitem()
|
|
if _debug: TestPulseConverter._debug(" - criteria: %r", criteria)
|
|
|
|
# get the list of subscriptions from the criteria
|
|
subscriptions = criteria.cov_subscriptions.cov_subscriptions
|
|
if _debug: TestPulseConverter._debug(" - subscriptions: %r", subscriptions)
|
|
assert len(subscriptions) == 1
|
|
|
|
def test_8_10_3(self):
|
|
"""Canceling a Subscription"""
|
|
if _debug: TestPulseConverter._debug("test_8_10_3")
|
|
|
|
# create a network
|
|
anet = ApplicationNetwork("test_8_10_3")
|
|
|
|
# add the ability to accept COV notifications to the TD
|
|
anet.td.add_capability(COVTestClientServices)
|
|
|
|
# tell the TD how to respond to confirmed notifications
|
|
anet.td.test_ack = True
|
|
anet.td.test_reject = None
|
|
anet.td.test_abort = None
|
|
|
|
# add the service capability to the IUT
|
|
anet.iut.add_capability(ChangeOfValueServices)
|
|
|
|
# make a pulse converter object
|
|
test_pc = PulseConverterObject(
|
|
objectIdentifier=('pulseConverter', 1),
|
|
objectName='pc',
|
|
presentValue=0.0,
|
|
statusFlags=[0, 0, 0, 0],
|
|
updateTime=DateTime(date=Date().now().value, time=Time().now().value),
|
|
covIncrement=10.0,
|
|
covPeriod=10,
|
|
)
|
|
|
|
# add it to the implementation
|
|
anet.iut.add_object(test_pc)
|
|
|
|
# wait for the subscription, then for the cancelation
|
|
anet.iut.start_state.doc("8.10.3-1-0") \
|
|
.receive(SubscribeCOVRequest).doc("8.10.3-1-1") \
|
|
.receive(SubscribeCOVRequest).doc("8.10.3-1-2") \
|
|
.success()
|
|
|
|
# send the subscription, wait for the ack, then send the cancelation
|
|
# and wait for the ack. Ignore the notification that is sent when
|
|
# after the subscription
|
|
anet.td.start_state.doc("8.10.3-2-0") \
|
|
.send(SubscribeCOVRequest(
|
|
destination=anet.iut.address,
|
|
subscriberProcessIdentifier=1,
|
|
monitoredObjectIdentifier=('pulseConverter', 1),
|
|
issueConfirmedNotifications=False,
|
|
lifetime=30,
|
|
)).doc("8.10.3-2-1") \
|
|
.ignore(UnconfirmedCOVNotificationRequest) \
|
|
.receive(SimpleAckPDU).doc("8.10.3-2-2") \
|
|
.send(SubscribeCOVRequest(
|
|
destination=anet.iut.address,
|
|
subscriberProcessIdentifier=1,
|
|
monitoredObjectIdentifier=('pulseConverter', 1),
|
|
)).doc("8.10.3-2-1") \
|
|
.ignore(UnconfirmedCOVNotificationRequest) \
|
|
.receive(SimpleAckPDU).doc("8.10.3-2-2") \
|
|
.success()
|
|
|
|
# run the group
|
|
anet.run()
|
|
|
|
def test_8_10_4(self):
|
|
"""Requests 8 Hour Lifetimes"""
|
|
if _debug: TestPulseConverter._debug("test_8_10_4")
|
|
|
|
# create a network
|
|
anet = ApplicationNetwork("test_8_10_4")
|
|
|
|
# add the ability to accept COV notifications to the TD
|
|
anet.td.add_capability(COVTestClientServices)
|
|
|
|
# tell the TD how to respond to confirmed notifications
|
|
anet.td.test_ack = True
|
|
anet.td.test_reject = None
|
|
anet.td.test_abort = None
|
|
|
|
# add the service capability to the IUT
|
|
anet.iut.add_capability(ChangeOfValueServices)
|
|
|
|
# make a pulse converter object
|
|
test_pc = PulseConverterObject(
|
|
objectIdentifier=('pulseConverter', 1),
|
|
objectName='pc',
|
|
presentValue=0.0,
|
|
statusFlags=[0, 0, 0, 0],
|
|
updateTime=DateTime(date=Date().now().value, time=Time().now().value),
|
|
covIncrement=10.0,
|
|
covPeriod=10,
|
|
)
|
|
|
|
# add it to the implementation
|
|
anet.iut.add_object(test_pc)
|
|
|
|
# wait for the subscription
|
|
anet.iut.start_state.doc("8.10.4-1-0") \
|
|
.receive(SubscribeCOVRequest).doc("8.10.4-1-1") \
|
|
.success()
|
|
|
|
# send the subscription, wait for the ack
|
|
anet.td.start_state.doc("8.10.4-2-0") \
|
|
.send(SubscribeCOVRequest(
|
|
destination=anet.iut.address,
|
|
subscriberProcessIdentifier=1,
|
|
monitoredObjectIdentifier=('pulseConverter', 1),
|
|
issueConfirmedNotifications=True,
|
|
lifetime=28800,
|
|
)).doc("8.10.4-2-1") \
|
|
.receive(SimpleAckPDU).doc("8.10.4-2-2") \
|
|
.success()
|
|
|
|
# run the group
|
|
anet.run()
|
|
|
|
def test_9_10_1_1(self):
|
|
if _debug: TestPulseConverter._debug("test_9_10_1_1")
|
|
|
|
notification_fail_time = 0.5
|
|
|
|
# create a network
|
|
anet = ApplicationNetwork("test_9_10_1_1")
|
|
|
|
# add the ability to accept COV notifications to the TD
|
|
anet.td.add_capability(COVTestClientServices)
|
|
|
|
# tell the TD how to respond to confirmed notifications
|
|
anet.td.test_ack = True
|
|
anet.td.test_reject = None
|
|
anet.td.test_abort = None
|
|
|
|
# add the service capability to the IUT
|
|
anet.iut.add_capability(ChangeOfValueServices)
|
|
|
|
# make a pulse converter object
|
|
test_pc = PulseConverterObject(
|
|
objectIdentifier=('pulseConverter', 1),
|
|
objectName='pc',
|
|
presentValue=0.0,
|
|
statusFlags=[0, 0, 0, 0],
|
|
updateTime=DateTime(date=Date().now().value, time=Time().now().value),
|
|
covIncrement=10.0,
|
|
covPeriod=10,
|
|
)
|
|
|
|
# add it to the implementation
|
|
anet.iut.add_object(test_pc)
|
|
|
|
# wait for the subscription, wait for the notification ack
|
|
anet.iut.start_state.doc("9.10.1.1-1-0") \
|
|
.receive(SubscribeCOVRequest).doc("9.10.1.1-1-1") \
|
|
.receive(SimpleAckPDU).doc("9.10.1.1-1-2") \
|
|
.timeout(10).doc("9.10.1.1-1-3") \
|
|
.success()
|
|
|
|
# test device is quiet
|
|
wait_for_notification = \
|
|
anet.td.start_state.doc("9.10.1.1-2-0") \
|
|
.send(SubscribeCOVRequest(
|
|
destination=anet.iut.address,
|
|
subscriberProcessIdentifier=1,
|
|
monitoredObjectIdentifier=('pulseConverter', 1),
|
|
issueConfirmedNotifications=True,
|
|
lifetime=30,
|
|
)).doc("9.10.1.1-2-1") \
|
|
.receive(SimpleAckPDU).doc("9.10.1.1-2-2")
|
|
|
|
# after the ack, don't wait too long for the notification
|
|
wait_for_notification \
|
|
.timeout(notification_fail_time).doc("9.10.1.1-2-3").fail()
|
|
|
|
# if the notification is received, success
|
|
wait_for_notification \
|
|
.receive(ConfirmedCOVNotificationRequest).doc("9.10.1.1-2-4") \
|
|
.timeout(10).doc("9.10.1.1-2-5") \
|
|
.success()
|
|
|
|
# run the group
|
|
anet.run()
|
|
|
|
def test_no_traffic(self):
|
|
"""Test basic configuration of a network."""
|
|
if _debug: TestPulseConverter._debug("test_no_traffic")
|
|
|
|
# create a network
|
|
anet = ApplicationNetwork("test_no_traffic")
|
|
|
|
# add the service capability to the IUT
|
|
anet.iut.add_capability(ChangeOfValueServices)
|
|
|
|
# make a pulse converter object
|
|
test_pc = PulseConverterObject(
|
|
objectIdentifier=('pulseConverter', 1),
|
|
objectName='pc',
|
|
presentValue=0.0,
|
|
statusFlags=[0, 0, 0, 0],
|
|
updateTime=DateTime(date=Date().now().value, time=Time().now().value),
|
|
covIncrement=10.0,
|
|
covPeriod=10,
|
|
)
|
|
|
|
# an easy way to change the present value
|
|
write_test_pc = lambda v: setattr(test_pc, 'presentValue', v)
|
|
|
|
# add it to the implementation
|
|
anet.iut.add_object(test_pc)
|
|
|
|
# make some transitions
|
|
anet.iut.start_state.doc("1-1-0") \
|
|
.call(write_test_pc, 100.0).doc("1-1-1") \
|
|
.timeout(1).doc("1-1-2") \
|
|
.call(write_test_pc, 0.0).doc("1-1-3") \
|
|
.timeout(1).doc("1-1-4") \
|
|
.success()
|
|
|
|
# test device is quiet
|
|
anet.td.start_state.timeout(5).success()
|
|
|
|
# run the group
|
|
anet.run()
|
|
|
|
def test_8_2_1(self):
|
|
"""To verify that the IUT can initiate ConfirmedCOVNotification service
|
|
requests conveying a change of the Present_Value property of Analog
|
|
Input, Analog Output, and Analog Value objects."""
|
|
if _debug: TestPulseConverter._debug("test_8_2_1")
|
|
|
|
# create a network
|
|
anet = ApplicationNetwork("test_8_2_1")
|
|
|
|
# add the ability to accept COV notifications to the TD
|
|
anet.td.add_capability(COVTestClientServices)
|
|
|
|
# tell the TD how to respond to confirmed notifications
|
|
anet.td.test_ack = True
|
|
anet.td.test_reject = None
|
|
anet.td.test_abort = None
|
|
|
|
# add the service capability to the IUT
|
|
anet.iut.add_capability(ChangeOfValueServices)
|
|
|
|
# make a pulse converter object
|
|
test_pc = PulseConverterObject(
|
|
objectIdentifier=('pulseConverter', 1),
|
|
objectName='pc',
|
|
presentValue=0.0,
|
|
statusFlags=[0, 0, 0, 0],
|
|
updateTime=DateTime(date=Date().now().value, time=Time().now().value),
|
|
covIncrement=10.0,
|
|
covPeriod=10,
|
|
)
|
|
|
|
# an easy way to change the present value
|
|
def write_test_pc(v):
|
|
if _debug: TestPulseConverter._debug("=== marco %r", v)
|
|
setattr(test_pc, 'presentValue', v)
|
|
if _debug: TestPulseConverter._debug("=== polo")
|
|
|
|
# add it to the implementation
|
|
anet.iut.add_object(test_pc)
|
|
|
|
# receive the subscription request, wait until the client has
|
|
# received the ack and the 'instant' notification. Then change the
|
|
# value a little bit and nothing should be sent. Change it some more
|
|
# and wait for the notification ack.
|
|
anet.iut.start_state.doc("2-1-0") \
|
|
.receive(SubscribeCOVRequest).doc("2-1-1") \
|
|
.receive(SimpleAckPDU).doc("2-1-2") \
|
|
.wait_event("e1").doc("2-1-3") \
|
|
.call(write_test_pc, 5.0).doc("2-1-4") \
|
|
.timeout(5).doc("2-1-5") \
|
|
.call(write_test_pc, 10.0).doc("2-1-6") \
|
|
.receive(SimpleAckPDU).doc("2-1-7") \
|
|
.receive(SimpleAckPDU).doc("2-1-8") \
|
|
.timeout(10).doc("2-1-9") \
|
|
.success()
|
|
|
|
# send the subscription request, wait for the ack and the 'instant'
|
|
# notification, set the event so the IUT can continue, then wait
|
|
# for the next notification
|
|
anet.td.start_state.doc("2-2-0") \
|
|
.send(SubscribeCOVRequest(
|
|
destination=anet.iut.address,
|
|
subscriberProcessIdentifier=1,
|
|
monitoredObjectIdentifier=('pulseConverter', 1),
|
|
issueConfirmedNotifications=True,
|
|
lifetime=30,
|
|
)).doc("2-2-1") \
|
|
.receive(SimpleAckPDU).doc("2-2-2") \
|
|
.receive(ConfirmedCOVNotificationRequest).doc("2-2-3") \
|
|
.set_event("e1").doc("2-2-4") \
|
|
.receive(ConfirmedCOVNotificationRequest).doc("2-2-5") \
|
|
.receive(ConfirmedCOVNotificationRequest).doc("2-2-6") \
|
|
.timeout(10).doc("2-2-7") \
|
|
.success()
|
|
|
|
# run the group
|
|
anet.run()
|
|
|
|
def test_simple_transition_unconfirmed(self):
|
|
if _debug: TestPulseConverter._debug("test_simple_transition_unconfirmed")
|
|
|
|
# create a network
|
|
anet = ApplicationNetwork("test_simple_transition_unconfirmed")
|
|
|
|
# add the ability to accept COV notifications to the TD
|
|
anet.td.add_capability(COVTestClientServices)
|
|
|
|
# tell the TD how to respond to confirmed notifications
|
|
anet.td.test_ack = True
|
|
anet.td.test_reject = None
|
|
anet.td.test_abort = None
|
|
|
|
# add the service capability to the IUT
|
|
anet.iut.add_capability(ChangeOfValueServices)
|
|
|
|
# make a pulse converter object
|
|
test_pc = PulseConverterObject(
|
|
objectIdentifier=('pulseConverter', 1),
|
|
objectName='pc',
|
|
presentValue=0.0,
|
|
statusFlags=[0, 0, 0, 0],
|
|
updateTime=DateTime(date=Date().now().value, time=Time().now().value),
|
|
covIncrement=10.0,
|
|
covPeriod=10,
|
|
)
|
|
|
|
# an easy way to change the present value
|
|
write_test_pc = lambda v: setattr(test_pc, 'presentValue', v)
|
|
|
|
# add it to the implementation
|
|
anet.iut.add_object(test_pc)
|
|
|
|
# receive the subscription request, wait until the client has
|
|
# received the ack and the 'instant' notification. Then change the
|
|
# value, no ack coming back
|
|
anet.iut.start_state.doc("3-1-0") \
|
|
.receive(SubscribeCOVRequest).doc("3-1-1") \
|
|
.wait_event("e1").doc("3-1-2") \
|
|
.call(write_test_pc, 100.0).doc("3-1-3") \
|
|
.timeout(10).doc("3-2-4") \
|
|
.success()
|
|
|
|
# test device is quiet
|
|
anet.td.start_state.doc("3-2-0") \
|
|
.send(SubscribeCOVRequest(
|
|
destination=anet.iut.address,
|
|
subscriberProcessIdentifier=1,
|
|
monitoredObjectIdentifier=('pulseConverter', 1),
|
|
issueConfirmedNotifications=False,
|
|
lifetime=30,
|
|
)).doc("3-2-1") \
|
|
.receive(SimpleAckPDU).doc("3-2-2") \
|
|
.receive(UnconfirmedCOVNotificationRequest).doc("3-2-3") \
|
|
.set_event("e1").doc("3-2-4") \
|
|
.receive(UnconfirmedCOVNotificationRequest).doc("3-2-5") \
|
|
.timeout(10).doc("3-2-6") \
|
|
.success()
|
|
|
|
# run the group
|
|
anet.run()
|
|
|
|
def test_changing_status_flags(self):
|
|
"""This test changes the status flags of binary value point to verify
|
|
that the detection picks up other changes, most tests just change the
|
|
present value."""
|
|
if _debug: TestPulseConverter._debug("test_changing_status_flags")
|
|
|
|
# create a network
|
|
anet = ApplicationNetwork("test_changing_status_flags")
|
|
|
|
# add the ability to accept COV notifications to the TD
|
|
anet.td.add_capability(COVTestClientServices)
|
|
|
|
# tell the TD how to respond to confirmed notifications
|
|
anet.td.test_ack = True
|
|
anet.td.test_reject = None
|
|
anet.td.test_abort = None
|
|
|
|
# add the service capability to the IUT
|
|
anet.iut.add_capability(ChangeOfValueServices)
|
|
|
|
# make a pulse converter object
|
|
test_pc = PulseConverterObject(
|
|
objectIdentifier=('pulseConverter', 1),
|
|
objectName='pc',
|
|
presentValue=0.0,
|
|
statusFlags=[0, 0, 0, 0],
|
|
updateTime=DateTime(date=Date().now().value, time=Time().now().value),
|
|
covIncrement=10.0,
|
|
covPeriod=10,
|
|
)
|
|
|
|
# an easy way to change the present value
|
|
def test_pc_fault():
|
|
if _debug: TestPulseConverter._debug("test_pc_fault")
|
|
test_pc.statusFlags = [0, 1, 0, 0]
|
|
|
|
# add it to the implementation
|
|
anet.iut.add_object(test_pc)
|
|
|
|
# receive the subscription request, wait until the client has
|
|
# received the ack and the 'instant' notification. Then change the
|
|
# value, no ack coming back
|
|
anet.iut.start_state.doc("4-1-0") \
|
|
.receive(SubscribeCOVRequest).doc("4-1-1") \
|
|
.wait_event("e1").doc("4-1-2") \
|
|
.call(test_pc_fault).doc("4-1-3") \
|
|
.timeout(10).doc("4-2-4") \
|
|
.success()
|
|
|
|
# test device is quiet
|
|
anet.td.start_state.doc("4-2-0") \
|
|
.send(SubscribeCOVRequest(
|
|
destination=anet.iut.address,
|
|
subscriberProcessIdentifier=1,
|
|
monitoredObjectIdentifier=('pulseConverter', 1),
|
|
issueConfirmedNotifications=False,
|
|
lifetime=30,
|
|
)).doc("4-2-1") \
|
|
.receive(SimpleAckPDU).doc("4-2-2") \
|
|
.receive(UnconfirmedCOVNotificationRequest).doc("4-2-3") \
|
|
.set_event("e1").doc("4-2-4") \
|
|
.receive(UnconfirmedCOVNotificationRequest).doc("4-2-5") \
|
|
.timeout(10).doc("4-2-6") \
|
|
.success()
|
|
|
|
# run the group
|
|
anet.run()
|
|
|
|
def test_changing_properties(self):
|
|
"""This test changes the value of multiple properties to verify that
|
|
only one COV notification is sent."""
|
|
if _debug: TestPulseConverter._debug("test_changing_properties")
|
|
|
|
# create a network
|
|
anet = ApplicationNetwork("test_changing_properties")
|
|
|
|
# add the ability to accept COV notifications to the TD
|
|
anet.td.add_capability(COVTestClientServices)
|
|
|
|
# tell the TD how to respond to confirmed notifications
|
|
anet.td.test_ack = True
|
|
anet.td.test_reject = None
|
|
anet.td.test_abort = None
|
|
|
|
# add the service capability to the IUT
|
|
anet.iut.add_capability(ChangeOfValueServices)
|
|
|
|
# make a pulse converter object
|
|
test_pc = PulseConverterObject(
|
|
objectIdentifier=('pulseConverter', 1),
|
|
objectName='pc',
|
|
presentValue=0.0,
|
|
statusFlags=[0, 0, 0, 0],
|
|
updateTime=DateTime(date=Date().now().value, time=Time().now().value),
|
|
covIncrement=10.0,
|
|
covPeriod=10,
|
|
)
|
|
|
|
# an easy way to change the present value
|
|
def test_pc_fault():
|
|
if _debug: TestPulseConverter._debug("test_pc_fault")
|
|
test_pc.presentValue = 100.0
|
|
test_pc.statusFlags = [0, 0, 1, 0]
|
|
|
|
# add it to the implementation
|
|
anet.iut.add_object(test_pc)
|
|
|
|
# receive the subscription request, wait until the client has
|
|
# received the ack and the 'instant' notification. Then change the
|
|
# value, no ack coming back
|
|
anet.iut.start_state.doc("5-1-0") \
|
|
.receive(SubscribeCOVRequest).doc("5-1-1") \
|
|
.wait_event("e1").doc("5-1-2") \
|
|
.call(test_pc_fault).doc("5-1-3") \
|
|
.timeout(10).doc("5-2-4") \
|
|
.success()
|
|
|
|
# test device is quiet
|
|
anet.td.start_state.doc("5-2-0") \
|
|
.send(SubscribeCOVRequest(
|
|
destination=anet.iut.address,
|
|
subscriberProcessIdentifier=1,
|
|
monitoredObjectIdentifier=('pulseConverter', 1),
|
|
issueConfirmedNotifications=False,
|
|
lifetime=30,
|
|
)).doc("5-2-1") \
|
|
.receive(SimpleAckPDU).doc("5-2-2") \
|
|
.receive(UnconfirmedCOVNotificationRequest).doc("5-2-3") \
|
|
.set_event("e1").doc("5-2-4") \
|
|
.receive(UnconfirmedCOVNotificationRequest).doc("5-2-5") \
|
|
.timeout(10).doc("5-2-6") \
|
|
.success()
|
|
|
|
# run the group
|
|
anet.run()
|
|
|
|
def test_multiple_subscribers(self):
|
|
"""This has more than one subscriber for the object."""
|
|
if _debug: TestPulseConverter._debug("test_multiple_subscribers")
|
|
|
|
# create a network
|
|
anet = ApplicationNetwork("test_multiple_subscribers")
|
|
|
|
# add the ability to accept COV notifications to the TD
|
|
anet.td.add_capability(COVTestClientServices)
|
|
|
|
# tell the TD how to respond to confirmed notifications
|
|
anet.td.test_ack = True
|
|
anet.td.test_reject = None
|
|
anet.td.test_abort = None
|
|
|
|
# add the service capability to the IUT
|
|
anet.iut.add_capability(ChangeOfValueServices)
|
|
|
|
# make a pulse converter object
|
|
test_pc = PulseConverterObject(
|
|
objectIdentifier=('pulseConverter', 1),
|
|
objectName='pc',
|
|
presentValue=0.0,
|
|
statusFlags=[0, 0, 0, 0],
|
|
updateTime=DateTime(date=Date().now().value, time=Time().now().value),
|
|
covIncrement=10.0,
|
|
covPeriod=10,
|
|
)
|
|
|
|
# an easy way to change both the present value and status flags
|
|
# which should trigger only one notification
|
|
def test_pc_fault():
|
|
if _debug: TestPulseConverter._debug("test_pc_fault")
|
|
test_pc.presentValue = 100.0
|
|
test_pc.statusFlags = [0, 0, 1, 0]
|
|
|
|
# add it to the implementation
|
|
anet.iut.add_object(test_pc)
|
|
|
|
# add another test device object
|
|
anet.td2_device_object = LocalDeviceObject(
|
|
objectName="td2",
|
|
objectIdentifier=('device', 30),
|
|
maxApduLengthAccepted=1024,
|
|
segmentationSupported='noSegmentation',
|
|
vendorIdentifier=999,
|
|
)
|
|
|
|
# another test device
|
|
anet.td2 = ApplicationStateMachine(anet.td2_device_object, anet.vlan)
|
|
anet.td2.add_capability(COVTestClientServices)
|
|
anet.append(anet.td2)
|
|
|
|
# receive the subscription requests, wait until both clients have
|
|
# received the ack and the 'instant' notification. Then change the
|
|
# value, no ack coming back
|
|
anet.iut.start_state.doc("6-1-0") \
|
|
.receive(SubscribeCOVRequest, pduSource=anet.td.address).doc("6-1-1") \
|
|
.receive(SubscribeCOVRequest, pduSource=anet.td2.address).doc("6-1-2") \
|
|
.wait_event("e2").doc("6-1-3") \
|
|
.call(test_pc_fault).doc("6-1-4") \
|
|
.timeout(10).doc("6-2-5") \
|
|
.success()
|
|
|
|
# first test device; send the subscription request, get an ack
|
|
# followed by the 'instant' notification
|
|
anet.td.start_state.doc("6-2-0") \
|
|
.send(SubscribeCOVRequest(
|
|
destination=anet.iut.address,
|
|
subscriberProcessIdentifier=1,
|
|
monitoredObjectIdentifier=('pulseConverter', 1),
|
|
issueConfirmedNotifications=False,
|
|
lifetime=30,
|
|
)).doc("6-2-1") \
|
|
.receive(SimpleAckPDU).doc("6-2-2") \
|
|
.receive(UnconfirmedCOVNotificationRequest).doc("6-2-3") \
|
|
.set_event("e1").doc("6-2-4") \
|
|
.receive(UnconfirmedCOVNotificationRequest).doc("6-2-5") \
|
|
.timeout(10).doc("6-2-6") \
|
|
.success()
|
|
|
|
# same pattern for the other test device
|
|
anet.td2.start_state.doc("6-3-0") \
|
|
.wait_event("e1").doc("6-3-1") \
|
|
.send(SubscribeCOVRequest(
|
|
destination=anet.iut.address,
|
|
subscriberProcessIdentifier=1,
|
|
monitoredObjectIdentifier=('pulseConverter', 1),
|
|
issueConfirmedNotifications=False,
|
|
lifetime=30,
|
|
)).doc("6-3-2") \
|
|
.receive(SimpleAckPDU).doc("6-3-3") \
|
|
.receive(UnconfirmedCOVNotificationRequest).doc("6-3-4") \
|
|
.set_event("e2").doc("6-3-5") \
|
|
.receive(UnconfirmedCOVNotificationRequest).doc("6-3-6") \
|
|
.timeout(10).doc("6-3-7") \
|
|
.success()
|
|
|
|
# run the group
|
|
anet.run()
|
|
|