mirror of
				https://github.com/3cky/mbusd
				synced 2025-10-26 23:46:44 +08:00 
			
		
		
		
	
		
			
				
	
	
		
			91 lines
		
	
	
		
			2.7 KiB
		
	
	
	
		
			Groff
		
	
	
	
	
	
			
		
		
	
	
			91 lines
		
	
	
		
			2.7 KiB
		
	
	
	
		
			Groff
		
	
	
	
	
	
| .TH "mbusd" 8 "25 Apr 2016" "mbusd @VERSION@"
 | |
| .SH NAME
 | |
| mbusd \- MODBUS/TCP to MODBUS/RTU gateway.
 | |
| .SH SYNOPSIS
 | |
| .B mbusd
 | |
| .RB [ -h ]
 | |
| .RB [ -d ]
 | |
| .RB [ -t ]
 | |
| .RB [ -y
 | |
| .IR file ]
 | |
| .RB [ -Y
 | |
| .IR file ]
 | |
| .RB [ -v
 | |
| .IR level ]
 | |
| .RB [ -L
 | |
| .IR logfile ]
 | |
| .RB [ -p
 | |
| .IR device ]
 | |
| .RB [ -s
 | |
| .IR speed ]
 | |
| .RB [ -m
 | |
| .IR mode ]
 | |
| .RB [ -P
 | |
| .IR port ]
 | |
| .RB [ -C
 | |
| .IR maxconn ]
 | |
| .RB [ -N
 | |
| .IR retries ]
 | |
| .RB [ -R
 | |
| .IR pause ]
 | |
| .RB [ -W
 | |
| .IR wait ]
 | |
| .RB [ -T
 | |
| .IR timeout ]
 | |
| .SH DESCRIPTION
 | |
| \fImbusd\fR is MODBUS/TCP to MODBUS/RTU gateway.
 | |
| .SH OPTIONS
 | |
| .IP \fB-h\fR
 | |
| Usage help.
 | |
| .IP \fB-d\fR
 | |
| Instruct \fImbusd\fR not to fork itself (non-daemonize).
 | |
| .IP \fB-t\fR
 | |
| Enable RTS RS-485 data direction control (if not disabled while compile).
 | |
| .IP "\fB-y \fIfile\fR"
 | |
| Enable RS-485 direction data direction control by writing '1' to file
 | |
| for transmitter enable and '0' to file for transmitter disable
 | |
| .IP "\fB-Y \fIfile\fR"
 | |
| Enable RS-485 direction data direction control by writing '0' to file
 | |
| for transmitter enable and '1' to file for transmitter disable
 | |
| .IP "\fB-v \fIlevel\fR"
 | |
| Specifies log verbosity level. 0 enables logging of errors only,
 | |
| 1 also enables warnings and 2 enables information messages.
 | |
| If \fImbusd\fR was compiled in debug mode, valid log levels are up to 9,
 | |
| where log levels above 2 forces logging of information about additional
 | |
| internal events.
 | |
| .IP "\fB-L \fIlogfile\fR"
 | |
| Specifies log file name ('-' for logging to STDOUT only, default is /var/log/mbusd.log).
 | |
| .IP "\fB-p \fIdevice\fR"
 | |
| Specifies serial port device name.
 | |
| .IP "\fB-s \fIspeed\fR"
 | |
| Specifies serial port speed.
 | |
| .IP "\fB-m \fImode\fR"
 | |
| Specifies serial port mode (like 8N1).
 | |
| .IP "\fB-P \fIport\fR"
 | |
| Specifies TCP port number.
 | |
| .IP "\fB-C \fImaxconn\fR"
 | |
| Specifies maximum number of simultaneous TCP connections.
 | |
| .IP "\fB-N \fIretries\fR"
 | |
| Specifies maximum number of request retries (0 - disable retries).
 | |
| .IP "\fB-R \fIpause\fR"
 | |
| Specifies pause between requests in milliseconds.
 | |
| .IP "\fB-W \fIwait\fR"
 | |
| Specifies response wait time in milliseconds.
 | |
| .IP "\fB-T \fItimeout\fR"
 | |
| Specifies connection timeout value in seconds (0 - disable timeout).
 | |
| .SH NOTES
 | |
| In case of situation when \fImbusd\fR received response with invalid CRC and can't correct
 | |
| error by re-request, it return MODBUS/TCP packet with exception code 04. In case of situation
 | |
| when \fImbusd\fR can't receive response from MODBUS RTU device (e.g. addressed controller
 | |
| is not present on the network), it return MODBUS/TCP packet with exception code 0x0B.
 | |
| .SH BUGS
 | |
| Broadcast messaging on MODBUS network isn't supported.
 | |
| 
 | |
| Please send bug reports to author.
 | |
| .SH AUTHORS
 | |
| Victor Antonovich <v.antonovich@gmail.com>
 | |
| 
 | |
| Andrew Denysenko <nitr0@seti.kr.ua>
 | |
| .SH LICENSE
 | |
| This program is distributed under BSD license. See LICENSE file in the installation directory for the full license text.
 | 